Logo image
Operations of the dominant harmonic active filter (DHAF) under realistic utility conditions
Conference paper

Operations of the dominant harmonic active filter (DHAF) under realistic utility conditions

Po-Tai Cheng, Subhashish Bhattacharya and Deepak Divan
Conference Record - IAS Annual Meeting (IEEE Industry Applications Society), Vol.4, pp.2135-2142
2000

Abstract

This paper presents laboratory test results of the Dominant Harmonic Active Filter (DHAF) prototype. The DHAF system achieves harmonic isolation at the dominant harmonics using square-wave active filter inverter. The key advantages of the DHAF system are the low rating and low bandwidth requirements of the active filter inverter. Such characteristics allow cost-effective and viable applications of the DHAF system to mitigate harmonic problems for high power nonlinear loads (10-100 MW and above). Several practical situations, including source-sink resonance, ambient harmonic interferences, and unbalance grid voltages are applied to the DHAF prototype to validate its performance. The operation principles of the DHAF system and the synchronous reference frame (SRF) based controller are discussed to explain how harmonic isolation at the dominant harmonics is accomplished. A design example of the DHAF system for a 20 MVA rectifier load at an industrial site is also given to illustrate its application.