3C strategy for inverters in parallel operation achieving an equal current distribution
Journal article   Peer reviewed

3C strategy for inverters in parallel operation achieving an equal current distribution

Wu Tsai-Fu, and Yu-Kai Chen
IEEE Transactions on Industrial Electronics, Vol.47(2), pp.273-281
2000

Abstract

A circular chain control (3C) strategy for inverters in parallel operation is presented in the paper, In the proposed inverter system, all the modules have the same circuit configuration, and each module includes an inner current loop and an outer voltage loop control. A proportional-integral controller is adopted as the inner current loop controller to expedite the dynamic response, while an H robust controller is adopted to reach the robustness of the multimodule inverter system and to reduce possible interactive effects among inverters. With the 3C strategy, the modules are in circular chain connection and each module has an inner current loop control to track the inductor current of its previous module, achieving an equal current distribution. Simulation results of two-module and a three-module inverter systems with different kinds of loads and with modular discrepancy have demonstrated the feasibility of the proposed control scheme. Hardware measurements are also presented to verify the theoretical discussion.