Logo image
A low-voltage ride-through technique for grid-connected converters of distributed energy resources
Journal article   Peer reviewed

A low-voltage ride-through technique for grid-connected converters of distributed energy resources

Chia-Tse Lee, Che-Wei Hsu and Po-Tai Cheng
IEEE Transactions on Industry Applications, Vol.47(4), pp.1821-1832
07/2011

Abstract

Distributed generation resources (DERs) grid-connected converter low-voltage ride-through (LVRT) reactive power
With more and more distributed energy resources (DERs) being installed, the utility requires these generation systems and their interface converters to remain grid connected during voltage sags to ensure the operating stability of the ac power system. These low-voltage ride-through (LVRT) requirements also suggest that the DER generation system injects real power and reactive power to support grid voltages. In this paper, a positive- and negative-sequence current injection method is proposed to meet the LVRT requirement. The proposed method imposes a predefined ampere constraint in its current injection to reduce the risk of overcurrent during the LVRT operation. Its operation principle and control method are explained and analyzed. Experimental results are presented to validate the effectiveness of the proposed method. Comparisons of the proposed method and other LVRT techniques are also presented. © 2011 IEEE.

Metrics

1 Record Views

Details

Logo image